Restaurant Fit-Out in Georgia: Hood, Exhaust and Makeup Air Before Plan Review

By Kiddio Engineering  ·  November 22, 2026  ·  11 min read
Restaurant Fit-Out in Georgia: Hood, Exhaust and Makeup Air Before Plan Review

A restaurant fit-out in Georgia answers to three reviewers.  The Building Department reviews the Mechanical drawings.  The Fire Marshal reviews the Type I hood, grease duct and fire suppression system.  The county Health Department reviews the kitchen layout and ventilation before construction starts.  When the hood, exhaust and makeup air design doesn’t line up across all three, comments pile up and the opening date slips.

Here is what each reviewer looks for, where Georgia departs from the model codes, and how to prepare a submittal that answers their questions up front.

Diagram: a Georgia restaurant kitchen is reviewed by the Building Department, the Fire Marshal and the Health Department, with the code basis for each

Two Codes Govern One Kitchen

Since January 1, 2026, Georgia has enforced the 2024 International Mechanical Code (IMC) with the 2026 Georgia Amendments.  Those amendments replace IMC Sections 506.1, 507.1 and 507.2.11.  Under the replacement text, Type I hoods, their grease ducts and exhaust equipment, and the fire suppression systems that protect them follow NFPA 96 and NFPA 101 as adopted and amended by the Georgia Insurance and Safety Fire Commissioner.  The Commissioner’s rules (Chapter 120-3-3) adopt the 2024 editions of both standards.

In practice, a Georgia kitchen is designed to two documents at once.  NFPA 96 governs the grease side.  The IMC governs everything else that moves air, including Type II hoods and makeup air.

The Fire Marshal Reviews the Grease Side

The local Fire Marshal enforces the state fire standards in counties of 100,000 or more and cities of 45,000 or more (O.C.G.A. § 25-2-12).  In most other areas, the State Fire Marshal’s office does.  For restaurants with an occupant load of 300 or more, or 100 or more where alcohol is served, the fire plans must be approved before any building permit is issued (O.C.G.A. §§ 25-2-13 and 25-2-14).

Confirm early who reviews your hood and suppression submittal.  That answer sets the order of your permits.

Type I or Type II: Start With the Cook Line

Hood type follows the equipment, so the equipment schedule has to be settled first.

  • Type I hoods are required where cooking appliances produce grease or smoke (IMC Section 507.2).  Fryers, griddles, charbroilers, ranges and woks fall here.
  • Type II hoods handle heat and steam, including most dishwashers, under the Health Department’s Food Service Design Manual.
  • The heaviest appliance sets the rate.  The manual applies the exhaust rate of the heaviest-duty appliance under a hood to the entire hood (Section Q, Item XII.1).

A frequent cause of comments is an equipment change after submittal.  A combi oven swapped for a charbroiler can turn a Type II hood into a Type I hood, which adds grease duct, suppression and Fire Marshal review.  Lock the cook line before the Mechanical design is final, and treat any later equipment change as a design change.

Hood placement limits from the Georgia DPH Food Service Design Manual: 6 in minimum overhang, hood bottom 6.5 to 7 ft above the floor, 4 ft maximum lip to cooking surface

Makeup Air: The Comment That Shows Up Most

Every cubic foot of air the hood pulls out has to come back in.  IMC Section 508.1 requires makeup air approximately equal to the exhaust, and mechanical makeup air must start and run together with the exhaust system.

Bar chart: 3,000 cfm of hood exhaust balanced by 2,400 cfm of makeup air and 600 cfm of transfer air, with IMC 508.1 and 508.1.1 rules

Three details draw comments:

  1. Temperature.  IMC Section 508.1.1 requires one of two things.  Either the kitchen’s HVAC system has the capacity to handle the makeup air load, or the makeup air is conditioned to within 10°F of the kitchen’s design setpoint.  Makeup air delivered through a compensating hood is excepted.
  2. Air balance.  Reviewers want to see where the air comes from.  Hood exhaust, dedicated makeup air, transfer air from the dining room and rooftop unit outdoor air should add up.  If they don’t, the space runs negative, doors pull hard and odors drift into the dining room.
  3. Windows and doors.  The Health Department’s design manual does not accept outside windows or doors as makeup air (Section Q, Item VIII.4).

Show the balance on the drawings, not only in the calculations.  A short air balance table on the Mechanical sheet answers the question before the reviewer asks it.

The Energy Code: A Model-Code Habit to Drop

Georgia’s Energy Code is the 2015 International Energy Conservation Code (IECC) with Georgia Supplements and Amendments.  The 2020 Georgia amendments delete 2015 IECC Section C403.2.8, Kitchen Exhaust Systems, and its table without substitution.  Designers who bring model-code habits from other states, such as the 10 percent limit on air supplied directly into the hood or the added measures above 5,000 cfm, may be designing to a section Georgia removed.

One caution: Georgia allows the COMcheck to follow either the 2015 IECC or ASHRAE 90.1-2013, and ASHRAE 90.1-2013 has its own kitchen exhaust provisions in Section 6.5.7.1.  Choose the compliance path deliberately, design to it, and make sure the COMcheck matches the drawings.

The Health Department Runs on Its Own Clock

Owners often treat Health Department approval as a final step.  In Georgia, it comes before construction.  Under Ga. Comp. R. & Regs. 511-6-1-.02(6)(b), plans for a new or extensively remodeled food service establishment go to the county Health Authority at least 14 business days before construction begins.  The Food Service Permit is issued only after plan approval and a preoperational inspection (511-6-1-.02(9)).

Four steps to a Georgia Food Service Permit: submit plans at least 14 business days before construction, plan approval, build, preoperational inspection

Ventless hoods are allowed only at the discretion of the Code Official or Health Authority (Section Q, Item IX.2.E.a).  Confirm acceptance before you build a layout around one.

A Pre-Submittal Checklist

Before the Mechanical drawings go in, confirm that the package shows:

  • A final equipment schedule with each appliance assigned to a Type I hood, a Type II hood or no hood
  • Hood exhaust rates based on the hood listing or the IMC capacity method, set by the heaviest-duty appliance under each hood
  • A makeup air schedule with source, airflow, tempering method and an interlock note
  • An air balance table that closes, including transfer air and rooftop unit outdoor air
  • Grease duct routing, clearances and roof termination coordinated with the NFPA 96 design
  • The COMcheck compliance path stated, with the kitchen exhaust design matched to it
  • Coordination among the Mechanical, Plumbing and fire suppression sheets, including grease interceptor and floor drain locations

Where We Fit In

Kiddio Engineering provides Commercial HVAC & Plumbing Design, Drawing & Code Review (from $400) and Permit Comment Response (from $400) for Georgia restaurant fit-outs.  We can review a design before it goes in or help answer comments after the fact.  We also prepare COMcheck reports, from $149.

Next step: Run the free Seal Check to see whether your restaurant plans need an engineer’s seal, or request a quote.

Georgia Codes Kitchen Hoods Makeup Air Plan Review Restaurant Fit-Out

General information only. Not engineering advice for a specific project. Requirements vary by jurisdiction.